- Power down the TX Modbus
- Set the rotary switch to position D
- Power up the TX Modbus and wait for at least 45s
- Power down the TX Modbus
- Set the rotary switch back to position 0
- Re-power the TX Modbus and connect it in Ethernet to the PC
- Check that the Ethernet settings on the PC are as follows:
IP address: 192.168.77.2
Subnet prefix length: 24
Gateway: 192.168.77.1
Preferred DNS: 8.8.8.8 - Access the server of the TX Modbus from your browser at 192.168.77.77