- The Pulse Low value increments up to 1,048,575. When the count reaches 1,048,576, Pulse Low returns to zero and Pulse High changes to 1. To have the correct count with the Pulse High and Low objects, it is therefore necessary to multiply the value in Pulse High by 1,048,576 and add it to that of Pulse Low.
- The total number of pulses is directly available in the Accumulator objects corresponding to each input:
- Input 1 = Pulse 1
- Input 2 = Pulse 2
- Input 3 = Open collector